400-671-8191

News & Events

Find our recent posts about corporate events and industrial news

   Home News & Events What to pay attention to when laying out integrated wiring cables

What to pay attention to when laying out integrated wiring cables

Release time: 2021-07-21 Source: Joryun Views: 267

QR:  What to pay attention to when laying out integrated wiring cables

Problems that should be paid attention to in wiring construction
(1) When the cable has excess cables at the two terminals, it should be cut to the required length instead of being rolled up and tied up.

(2) The distance of the unwound line segment at the cable joint should not exceed 2cm.If it is too long, it will cause greater near-end crosstalk.

(3) At the joint, the outer protective layer of the cable needs to be pressed in the joint and cannot be outside the joint. Because when the cable is subjected to external tension, the stressed part should be borne by the entire cable, otherwise the stress is the connection between the cable and the joint Metal parts.

(4) During the cable wiring construction, the cable tension is limited, generally about 9kg, this needs to be confirmed with the cable supplier. Excessive tension will damage the cable twisting, thereby reducing the use of the cable Performance.

0

Related Articles